Description

Product Overview

Spirax Sarco BC3150 is a microprocessor-based blowdown controller engineered for boiler water total dissolved solids (TDS) control and condensate contamination detection. Operating in conjunction with Spirax Sarco conductivity sensors and actuated blowdown valves, the controller regulates dissolved mineral concentration to prevent foaming, scaling, and boiler water carryover into steam mains. It eliminates manual chemical blowdown guesswork by continuously calculating liquid electrical conductivity and actuating motorized or solenoid blowdown valves when pre-set limits are exceeded.

Spirax Sarco BC3150 blowdown controller front panel and housing

The unit features a 3-digit backlit LCD screen and a tactile five-button silicone front membrane. Operational data is retained indefinitely in non-volatile Flash memory without battery backup. To protect configuration settings against unauthorized tampering, parameter adjustments require passcode entry, while routine calibration remains directly accessible from the main run menu for water treatment specialists.

Key Features

Spirax Sarco BC3150 keypad layout and front panel definitions

  • Four selectable measurement ranges spanning 0 to 9.99, 0 to 99.9, 0 to 999, and 0 to 9990 µS/cm or ppm with 0.1% full-scale resolution.
  • Universal power supply accepting 110 V to 240 Vac (99 V to 264 Vac operating window) at 50/60 Hz with maximum 7.5 W consumption.
  • Dual single-pole changeover (SPCO) relays rated at 3 A resistive at 250 Vac for valve actuation and alarm signaling.
  • Selectable valve actuation modes including continuous blowdown, timed purge cycle for line-mounted probes, and pulsed operation (10 seconds open, 20 seconds closed) to avoid low water cut-outs on small boilers.
  • Automatic temperature compensation via 3-wire or 4-wire Pt100 RTD (2%/°C slope), or selectable default fixed temperature between 100 °C and 250 °C (184 °C / 10 bar g factory default).
  • Electrochemical probe cleaning cycle delivering 32 Vdc pulsed drive (1 s on, 1 s off for 20 s) to remove scale from sensor tips.
  • Galvanically isolated 4-20 mA or 0-20 mA retransmission output into loads up to 500 ohms for building management systems (BMS) or data loggers.
  • Infrared (IR) slave communication port for linking parameter registers to adjacent Spirax Sarco master controllers with RS485 communication.
  • Sensor diagnostics providing real-time probe factor (PF) readings to assess scale buildup or short circuits without removing the sensor.

Technical Specifications

Electrical and Enclosure Data

ParameterSpecification
Mains Voltage Range110 V to 240 Vac (99 V to 264 Vac), 50/60 Hz
Power Consumption7.5 W maximum
Enclosure MaterialPolycarbonate body; silicone rubber front keypad (60 Shore)
Protection RatingFront face IP65 (TRAC Global) and NEMA 4 (UL); enclosure minimum IP54
Net Weight475 g
Ambient Operating Temperature0 °C to 55 °C (32 °F to 131 °F)
Maximum Altitude2,000 m (6,562 ft) above sea level
Maximum Relative Humidity80% up to 31 °C, decreasing linearly to 50% at 40 °C
Overvoltage CategoryCategory III (IEC 60364)
Pollution DegreeDegree 2 (as supplied), Degree 3 (installed in enclosure)
Safety & EMC ApprovalsEN 61010-1:2010, UL61010-1, CAN/CSA-C22.2 No. 61010-1, 2014/30/EU, VdTÜV Wasserüberwachung 100

Sensor Input and Signal Data

Input ParameterSpecification
Supported Conductivity ProbesSpirax Sarco CP10, CP30, CP32
Conductivity Measurement Ranges0-9.99, 0-99.9, 0-999, 0-9990 µS/cm or ppm
Minimum Conductivity Threshold≥ 1 µS/cm at 25 °C
Measurement Accuracy±2.5% FSD (±5% FSD on 0-9.999 range)
Resolution0.1% FSD
Conductivity Driveac, 4-wire connection
µS/cm to ppm Conversion Factor0.7 (neutralizing factor 0.7)
Temperature Sensor CompatibilityPt100 RTD (Class B or better, 3-wire or 4-wire)
Temperature Measurement Range0 °C to 250 °C (manual configuration 100 °C to 250 °C in 1 °C steps)
Temperature Accuracy & ResolutionAccuracy ±2.5% FSD (±5% system accuracy); resolution 1% FSD
Temperature Drivedc, 3-wire

Control and Output Data

Output FunctionSpecification
Relay Contacts2 × Single Pole Changeover (SPCO)
Relay Voltage Rating250 Vac maximum
Resistive Load3 A at 250 Vac
Inductive Load1 A at 250 Vac
AC Motor Load1/4 HP (2.9 A) at 250 Vac; 1/10 HP (3 A) at 120 Vac
Pilot Duty RatingC300 (2.5 A) for control circuits and coils
Relay Service LifeElectrical: ≥ 3 × 10⁵ operations; Mechanical: 30 × 10⁶ operations
Analog Retransmit Range0-20 mA or 4-20 mA (isolated up to 100 V)
Analog Open Circuit Voltage19 Vdc maximum
Analog Maximum Load500 ohms
Probe Cleaning Drive32 Vdc pulsed (1 s on, 1 s off, 20 s duration)

Default Factory Settings

Setting / CodeFactory DefaultAdjustable Range
Range Multiplier (rAn)×1000 (0 to 9990)×1, ×10, ×100, ×1000
UnitsµS/cm (ON)µS/cm (ON) or ppm (OFF)
Set Point (SP)50% FSD0 to 99.9% FSD (5% FSD fixed hysteresis)
Alarm Limit (AL)99.9% FSD0 to 99.9% FSD (3% FSD fixed hysteresis)
Alarm Latch (ALL)OFFON (lockout) or OFF
Purge Duration (Pur)0 s (continuous mode)0 to 99 seconds
Burner Interlock (bur)ON (cumulative firing)ON or OFF (every 30 minutes)
Input Filter (FLt)ON (64 s time constant)ON (64 s) or OFF (8 s delay, 5% jump out)
Pulsed Blowdown (PuL)OFF (continuous)ON (10 s open / 20 s closed) or OFF
Analog Output (rEt)4 mA (4-20 mA)0 mA or 4 mA base
Temperature Fallback (tC)184 °C (10 bar g)100 °C to 250 °C

Applications

Spirax Sarco BC3150 BCS1 boiler control system schematic

  • Steam Boiler TDS Control (BCS1 System): Boiler shell conductivity monitoring utilizing a CP30 sensor with continuous or pulsed blowdown actuation to maintain chemical concentrations within boiler manufacturer limits.
  • Blowdown Line TDS Control (BCS2 System): In-line conductivity monitoring using a CP10 sensor fitted with a timed purge cycle (0-99 s) to bring fresh boiler water samples past the probe tip prior to measurement.
  • Condensate Contamination Detection (CCD): Bypass-line monitoring of return condensate using CP10 sensors and Pt100 RTDs, actuating 3-port diverter valves (such as Spirax Sarco QL) or dual 2-port dump systems to isolate contaminated condensate from boiler feedtanks.

Spirax Sarco BC3150 condensate contamination detection CCD schematic

Mechanical & Panel Installation

Spirax Sarco BC3150 mounting outline and enclosure dimensions

Spirax Sarco BC3150 must be installed in a clean, vertical orientation within an enclosure rated to at least IP54 (or NEMA Type 3, 4, 4X, 6, or 13). Three mounting arrangements are supported:

  1. DIN Rail Mounting: Attach the supplied spring clip to the rear enclosure using the provided self-tapping screws. The rear housing provides two clip height options to suit panel clearances. Ensure the clip latches onto the 35 mm rail.
  2. Chassis Plate Mounting: Secure the casing using two M4 screws, nuts, and washers through the top and bottom slots. The casing must not be drilled.
  3. Panel Cutout Mounting: Cut the panel aperture according to template dimensions (minimum panel thickness 1 mm when using bezel). Apply the self-adhesive gasket to the front face, insert from the panel rear, and tighten the supplied M4 × 25 mm screws to 1.0–1.2 Nm. Never use screws exceeding 25 mm in length.

Maintain a minimum clearance of 15 mm between adjacent controllers to permit convection cooling, and ensure optical paths between neighboring units remain unblocked for infrared data exchange.

Electrical Wiring & Probe Connections

Spirax Sarco BC3150 signal circuit and probe wiring diagram

All electrical connections use plug-in screw clamp terminal blocks accepting 0.2 to 2.5 mm² (24 to 14 AWG) wiring, stripped to 5-6 mm. Overcurrent protection must be integrated into supply conductors (3 A fuse on mains and relay phases; 1 A fast-blow fuse on burner input).

  • Mains and Valve Terminals: Wire single-phase 110-240 Vac supply to terminals 1 (Live), 2 (Neutral), and 3 (Functional Earth). Connect blowdown valve circuits to terminals 21-23 and alarm loops to terminals 24-26. Relay contacts must share the phase of the mains feed.
  • Sensor Connections: Connect CP10 or CP30 probes using screened 4-core cable (1.0 to 1.5 mm², 18-16 AWG). Terminals 50 and 51 link to the probe active tip, while terminals 52 and 53 link to the probe body and pipework earth. Ensure body-to-pipe resistance is under 1 ohm.
  • Maximum Cable Lengths: Maximum allowable probe cable length is 100 m for the 0-9990 and 0-999 µS/cm ranges, 30 m for the 0-99.9 µS/cm range, and 10 m for the 0-9.99 µS/cm range.
  • Temperature Probe Connections: Connect 3-wire Pt100 RTDs to terminals 56, 57, and 58. For 4-wire sensors, link two common leads inside an external junction box and terminate to terminal 56, wiring the remaining two leads to 57 and 58.